Validation

How the calculators are checked

Every calculator runs the same engine, and that engine is checked three ways. The cases below run live in your browser on this page, using the same code as the calculators.

Live checks

CaseBasisExpectedCalculatedResult

1. Direct numerical integration

The automated tests integrate the defining integral of the configuration factor, cos θ₁ cos θ₂ / (π r²), numerically over the emitter. They do this for parallel rectangles centred on and offset from the receiver, and for perpendicular rectangles with and without a wing wall. The closed-form expressions used by the calculators agree to better than 2 × 10⁻⁵.

2. Physical limits

An infinite parallel plane gives φ = 1. A half-space seen from the corner of a perpendicular wall gives φ = 0.5, so the flux at the corner is half the emitted flux. An emitter seen edge-on gives φ = 0.

3. Worked cases from completed projects

Results stored in independently built spreadsheet calculators from completed boundary-opening and fire-severity assessments are reproduced to at least nine significant figures. Those spreadsheets use σ = 5.68 × 10⁻⁸ W/m²K⁴ and T + 273, so these cases use the IFEG constants.

Defaults that differ from common spreadsheets

The calculators default to σ = 5.670 × 10⁻⁸ W/m²K⁴ and T + 273.15. Many spreadsheets use the IFEG 2005 values, 5.68 × 10⁻⁸ and T + 273, and you can choose either. At 860 °C with ε = 0.9 the emitted flux is 84.14 kW/m² with the first set and 84.24 kW/m² with the second. Lengths such as the solid return wall are solved exactly and then rounded up. Some spreadsheets step along a 0.05 m grid instead, which gives 1.05 m where the exact value is 1.00 m.

Found a case that disagrees with your own calculation? Email tin@cavies.studio and it will be checked and added here.