Fire severity

Time equivalence: equivalent fire severity of a compartment

The time of exposure to the standard fire test that has the same effect as a complete burnout of the compartment, from its fire load, ventilation and linings (EN 1991-1-2 Annex F, as used in the International Fire Engineering Guidelines). Compare it with the proposed fire resistance level.

Inputs

Fire load
MJ/m²

Compartment
m²
m
m²
m²
Linings and member
min m²/MJ
min

The values shown are an example. Where the linings are not assessed, EN 1991-1-2 allows kb = 0.07. kc = 1.0 for protected steel, reinforced concrete and timber.

Result

Equivalent fire severity te
–min
Ventilation factor wf
–
Opening ratio αv
–

For your report

Af (m²)H (m)Av (m²)ef (MJ/m²)kbwfte (min)FRL (min)Result

Working

StepSymbolExpressionValueUnit

Method

te = ef kb wf kc, with the ventilation factor wf = (6/H)0.3 [0.62 + 90 (0.4 − αv)⁴ / (1 + bv αh)] ≥ 0.5. Here αv = Av/Af, αh = Ah/Af and bv = 12.5 (1 + 10αv − αv²) ≥ 10 (EN 1991-1-2 Annex F; IFEG 2005 section 2.6.1.3).

The formula applies for αv from 0.025 to 0.25 (EN 1991-1-2), and IFEG 2005 gives 0.05 to 0.25. IFEG also limits αh to 0.20. The calculator warns outside these ranges. The value for the report is rounded to the nearest minute. The comparison passes when the FRL exceeds te, both as calculated and as rounded for the report.

IFEG 2005 Table 3.4.1b: fire load density by occupancy (MJ/m²)
OccupancyMean80th90th95th
Dwelling780870920970
Hospital230350440520
Hospital storage2000300037004400
Hotel bedroom310400460510
Offices420570670760
Shops60090011001300
Manufacturing300470590720
Manufacturing and storage (< 150 kg/m²)1180180022402690
Libraries150022502550–
Schools285360410450

Variable fire loads (contents) only, from CIB W14 (1983). IFEG notes that at least the 95th percentile should be used for design.