Fire severity
Time equivalence: equivalent fire severity of a compartment
The time of exposure to the standard fire test that has the same effect as a complete burnout of the compartment, from its fire load, ventilation and linings (EN 1991-1-2 Annex F, as used in the International Fire Engineering Guidelines). Compare it with the proposed fire resistance level.
Result
For your report
| Af (m²) | H (m) | Av (m²) | ef (MJ/m²) | kb | wf | te (min) | FRL (min) | Result |
|---|---|---|---|---|---|---|---|---|
Working
| Step | Symbol | Expression | Value | Unit |
|---|
Method
te = ef kb wf kc, with the ventilation factor wf = (6/H)0.3 [0.62 + 90 (0.4 − αv)⁴ / (1 + bv αh)] ≥ 0.5. Here αv = Av/Af, αh = Ah/Af and bv = 12.5 (1 + 10αv − αv²) ≥ 10 (EN 1991-1-2 Annex F; IFEG 2005 section 2.6.1.3).
The formula applies for αv from 0.025 to 0.25 (EN 1991-1-2), and IFEG 2005 gives 0.05 to 0.25. IFEG also limits αh to 0.20. The calculator warns outside these ranges. The value for the report is rounded to the nearest minute. The comparison passes when the FRL exceeds te, both as calculated and as rounded for the report.
IFEG 2005 Table 3.4.1b: fire load density by occupancy (MJ/m²)
| Occupancy | Mean | 80th | 90th | 95th |
|---|---|---|---|---|
| Dwelling | 780 | 870 | 920 | 970 |
| Hospital | 230 | 350 | 440 | 520 |
| Hospital storage | 2000 | 3000 | 3700 | 4400 |
| Hotel bedroom | 310 | 400 | 460 | 510 |
| Offices | 420 | 570 | 670 | 760 |
| Shops | 600 | 900 | 1100 | 1300 |
| Manufacturing | 300 | 470 | 590 | 720 |
| Manufacturing and storage (< 150 kg/m²) | 1180 | 1800 | 2240 | 2690 |
| Libraries | 1500 | 2250 | 2550 | – |
| Schools | 285 | 360 | 410 | 450 |
Variable fire loads (contents) only, from CIB W14 (1983). IFEG notes that at least the 95th percentile should be used for design.